Connection
4.6 Connecting the Interface Module to a CM IM DP ECOFAST Cu Connection Module
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
87
4.6
Connecting the Interface Module to a CM IM DP ECOFAST Cu
Connection Module
Introduction
You wire the power supplies and PROFIBUS DP to the CM IM DP ECOFAST Cu connection
module using ECOFAST cable connectors.
X01
ECOFAST socket (with male contact insert) for feeding the supply voltages and
PROFIBUS DP
X02
ECOFAST socket (with female contact insert) for forwarding the supply voltages and
PROFIBUS DP
Requirements
●
The interface module (including the bus module) and the connection module are mounted
on the rack.
●
You have set the PROFIBUS DP address on the connection module according to your
configuration.
●
The terminating resistor must be activated if no loop cables are connected.
Required tools
Screwdriver, stripping and crimp tool for wiring the ECOFAST cable connector, if you are
fabricating your own cables.
Required accessories
●
PROFIBUS ECOFAST Hybrid Cable, preassembled at both ends with ECOFAST Hybrid
Plug 180. The patch cable is available in various lengths.
●
If you are fabricating your own cables:
–
PROFIBUS ECOFAST hybrid cable, unassembled
–
PROFIBUS ECOFAST Hybrid Plug 180 (ECOFAST Cu) with Hanbrid connector
–
PROFIBUS ECOFAST Hybrid Plug, angled, (ECOFAST Cu) with Hanbrid connector