EM-7801-U  Rev.3  P. 1 / 9

INSTRUCTION MANUAL

RELAY CONTACT OUTPUT MODULE, 8 points

(CC-Link V.1.10)

MODEL

R7C-DC8C

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Discrete output module.......................................................(1)
Terminating resistor (110 Ω, 0.5 W) ...................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2 and

Measurement Category II (output, transition voltage
1500V) with the maximum operating voltage 125V.

*1

  Ba-

sic insulation (output to power: 150V)

*2

 is maintained.

Prior to installation, check that the insulation class of
this unit satisfies the system requirements.

*1.  For use in Measurement Category I (output, transition

voltage 1500V) with the maximum operating voltage
250V.

*2. For use in Measurement Category I, 300V.

• The equipment must be mounted inside the instrument

panel of a metal enclosure.

• Altitude up to 2000 meters.
• The equipment must be installed such that appropriate

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system.  The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.

 

POWER INPUT RATING & OPERATIONAL RANG

• Locate the power input rating marked on the product and

confirm its operational range as indicated below:

24V DC rating: 24V ±10%, approx. 60mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and output signal for safety.

• DO NOT set the switches on the module while the power

is supplied.  The switches are used only for maintenance
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the

air, install the unit inside proper housing with sufficient
ventilation.

• Do not install the unit where it is subjected to continuous

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C

(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive

cable, high frequency line, etc.).

• Do not bind these cables together with those in which

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7C-DC8C

Page 1: ...ay invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL ...

Page 2: ...ddress 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Station Address Setting x1 Station Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Output at the loss of communication SW1 4 SW1 4 OUTPUT AT THE LOSS OF COMMUNICATION OFF Reset the output turned off ON Hol...

Page 3: ...N OFF BL OFF ON CRC error found in the data addressed to the station ON OFF BL OFF OFF ON OFF OFF BL ON Link is not started ON OFF OFF BL OFF ON OFF OFF OFF ON No data addressed to the station Or unable to receive data addressed to the station due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OF...

Page 4: ... 3 4 1 2 5 3 FG 6 7 24V DC 0V SLD DG DB DA 10 1 0V 24V Output Connection Example In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal 4 Points common 10 14 1 2 5 11 24V Y0 0V Y3 COM0 COM0 18 6 9 15 Y4 Y7 COM1 COM1 8 Points common 10 14 1 2 5 11 24V 24V DC Y0 0V Y3 15 Y4 18 Y7 COM0 COM0 6 9 COM1 COM1 24V DC 5 2 6 4 7 13 8 9 14...

Page 5: ...ATA ALLOCATION RY n 0 7 to RY n 0 0 Unused R7C DC8C 0 F 1F Interval timed Response X Unused 0 F 1F Refresh Data Y R7C DC8C I O DATA DESCRIPTIONS 0 15 Output 0 Output 1 Output 2 8 points Output 3 Output 7 Not Used Remains 0 0 OFF 1 ON DISCRETE OUTPUT WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongu...

Page 6: ... a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases by grounding the FG terminal remove the grounding When painting the internal plate of the con...

Page 7: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7C Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Page 8: ...tions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the im...

Page 9: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via CC Link ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic ...