R7C-DC8C

EM-7801-U  Rev.3  P. 5 / 9

COMMUNICATION CABLE CONNECTIONS

DA
DB

DG

SLD

FG

Master Unit

DA
DB

DG

SLD

FG

Remote Unit

DA
DB

DG

SLD

FG

Remote Unit

TERMINATOR

TERMINATOR

blue

white

yellow

Be sure to connect the terminating resistor included in the product package to the unit at both ends of communication line.
The terminator must be connected across DA and DB.
The Master Unit can be located other than at the extreme ends of communication line.

DATA ALLOCATION

RY(n+0)7 to RY(n+0)0

Unused

(R7C-DC8C)

0

F

1F

Interval-timed Response (X)

Unused

0

F

1F

Refresh Data (Y)

■ 

R7C-DC8C

I/O DATA DESCRIPTIONS

0

15

Output 0
Output 1
Output 2      8 points
Output 3
     : 
Output 7
Not Used (Remains “0”)

0 : OFF  
1 : ON 

■ 

DISCRETE OUTPUT

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7C-DC8C

Page 1: ...ay invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL ...

Page 2: ...ddress 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Station Address Setting x1 Station Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Output at the loss of communication SW1 4 SW1 4 OUTPUT AT THE LOSS OF COMMUNICATION OFF Reset the output turned off ON Hol...

Page 3: ...N OFF BL OFF ON CRC error found in the data addressed to the station ON OFF BL OFF OFF ON OFF OFF BL ON Link is not started ON OFF OFF BL OFF ON OFF OFF OFF ON No data addressed to the station Or unable to receive data addressed to the station due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OF...

Page 4: ... 3 4 1 2 5 3 FG 6 7 24V DC 0V SLD DG DB DA 10 1 0V 24V Output Connection Example In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal 4 Points common 10 14 1 2 5 11 24V Y0 0V Y3 COM0 COM0 18 6 9 15 Y4 Y7 COM1 COM1 8 Points common 10 14 1 2 5 11 24V 24V DC Y0 0V Y3 15 Y4 18 Y7 COM0 COM0 6 9 COM1 COM1 24V DC 5 2 6 4 7 13 8 9 14...

Page 5: ...ATA ALLOCATION RY n 0 7 to RY n 0 0 Unused R7C DC8C 0 F 1F Interval timed Response X Unused 0 F 1F Refresh Data Y R7C DC8C I O DATA DESCRIPTIONS 0 15 Output 0 Output 1 Output 2 8 points Output 3 Output 7 Not Used Remains 0 0 OFF 1 ON DISCRETE OUTPUT WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongu...

Page 6: ... a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases by grounding the FG terminal remove the grounding When painting the internal plate of the con...

Page 7: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7C Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Page 8: ...tions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the im...

Page 9: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via CC Link ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic ...

Reviews: