Rexroth IndraDrive FCS01.1
Installation
8-17
DOK-INDRV*--FCS01*****-IB01_EN-P
Position
Setting
Effect
0
Operation at the IT mains
1
Standard position (factory setting)
2
Reduced leakage current;
operation with earth-leakage circuit breakers
Fig. 8-21:
Jumper position bottom
Operation
Setting of
jumper at top of
device
Setting of jumper
at bottom of
device
Explanation
IT mains
0
0
Earth-leakage
circuit breaker
0, 1 or 2
2
Fig. 8-22:
Settings
Note:
Be aware that the specified degree of radio interference
suppression may change with the different settings. For
details, please refer to Chapter 13.4, Electromagnetic
Compatibility (EMC).
Effect of the settings in the device
L1
L2/N
L3
~
=
~
=
M
Oberseite (Netzeingang)
On top (mains)
Unterseite (Motorausgang)
Bottom (motor output)
Fig. 8-23:
Internal effect of the settings