15-60
Control Communication - Field Busses and Protocols
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
DeviceNet Error Monitoring and Indication
LED Indication at the Function Module FCC01.1F-DN
4 LEDs indicate the status at the function module:
•
MS/NS for the status of the DeviceNet bus
•
DS/DE for the status of the module
LED MS
red/gree
n
LED NS
red/gre
en
LED DS
(green)
LED DE
(red)
Significance
off
No supply voltage at the module
Green
on
The module is ready
Flashin
g green
The module is in standby
Flashin
g red
Confirmable error
Red on
Non-confirmable error,
modules possibly needs
replacement
OFF
Module is not online:
•
No supply voltage at the
module
•
The module could not execute
the Dup_MAC_ID test
Flashin
g green
Module is online and has
executed the Dup_MAC_ID test,
but did not establish a connection
to the other nodes
Green
on
Module is online and is connected
to a master
Flashin
g red
One or more I/O connections are
in timeout status
Red on
Module has detected an error that
makes communication
impossible, e.g. Bus-Off,
Dup_MAC_IC test error
OFF
No power supply
Flashin
g
Initialisation (init phase)
O (n)
Module OK
OFF
no error
Flashin
g ~ 5 Hz
Initialization phase
Flashin
g ~ 2 Hz
Timeout error
Flashin
g ~ 0.5
Hz
Converter error
O (n)
System error, e.g. plug-in contact
incorrect
Fig. 15-84: Diagnosis LED DeviceNet
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......