9-4
Indications and Operation of the Function Modules
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Standard Control Panel FCC01.1T-STD-NNNN
This function module is used as an easy-to-operate parameterization,
indication, and control tool of the FCS01 frequency converter.
Features
•
4-digit, 7-segment LED display
•
Direct control of a frequency converter
•
Indication of the active parameter record and operating value
•
Storage of a complete converter data record (parameter record 1…4)
Fig. 9-3:
Standard Control Panel FCC01.1T-STD-NNNN
After the standard control panel has been plugged on and the mains
voltage has been switched on, horizontal lines will be indicated in the 4-
digit, 7-segment display. They signal that the frequency converter is
operative. If a jog frequency value is preset in parameter P113, this value
will appear in the display.
When release is given for the frequency converter, the display will change
automatically to the operating value selected in parameter P001
>Selection of indicator value< (factory setting
current frequency).
The parameter record used currently is indicated in binary code by the 2
LEDs to the left of the display.
Note:
The factory setting for the digital frequency command value is
0Hz. To check whether the drive is working, enter a frequency
command value via the
key, or a jog frequency via the
respective parameter P113, >Jog frequency<.
Settings may only be made by qualified personnel under strict
observation of the safety instructions and warnings.
ATTENTION!: The drive will possibly start moving
immediately after the START key
has been pressed!
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......