11-38
Parameterization
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Parameter
Setting value / description / note
Device
Supervisor
Parameter record
P520
Flying restart circuit
S
P
0 ... 4
[ 0 ]
Suitable only fro motor frequencies < 100Hz.
This function is needed to lock on the FC to already rotating motors, e.g. with fan drives.
0 =
Switched off,
no flying restart circuit.
1 =
Both directions,
the FC searches a speed in both directions.
2 =
In direction of the setpoint value,
the FC searches only in the direction of the
applied setpoint value.
3 =
Both directions,
only after mains failure and error
4 =
In direction of the setpoint value,
only after mains failure and error
P521
Flying restart circuit
resolution
S
P
0.02... 2.50 Hz
[ 0.05 ]
With this parameter, the increment used for searching the flying restart circuit can be
modified. Excessively high values are detrimental to the accuracy and cause FC failure with
overcurrent message. Excessively small values greatly prolong searching time.
P522
Flying restart circuit offset
S
P
-10.0 ... 10.0
Hz
[ 0.0 ]
A frequency value which can be added to the found frequency value, for example to get
into the motor-driven range, to avoid the chopper range.
P523
Factory setting
0 ... 2
[ 0 ]
By addressing the corresponding value and confirmation with the Enter key, the selected
parameter range is set to factory setting. After the setting has been made, the value of the
parameter automatically changes back to 0.
0 =
No change.
Does not change the parameterization.
1 =
Load factory setting:
All parameterization of the FC is reset to factory setting.
All parameterized data is lost.
2 =
Factory setting without bus:
All parameters of the FC, but not the bus
parameters are reset to factory setting.
P535
I
2
t motor
S
0 ... 1
[ 0 ]
The motor temperature is calculated in dependence on the output current, the time and
the output frequency (cooling). Reaching of the temperature limit results in deactivation
and error message E002 (overtemperature motor). Here, environmental conditions cannot
be taken into consideration.
0 =
switched off
1 =
switched on
P536
Current limit
S
0.1 ... 2.0 / 2.1
[ 1.5 ]
The FC output current is limited to the set value. If this limit is reached, the FC reduces the
current output frequency.
Multiplier with the nominal FC current; makes up the limit value
Current limit value = P536 x nominal current
FC
2.1 = OFF
stands for deactivation of this limit value. This is also the basic setting of
this parameter.
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......