15-24
Control Communication - Field Busses and Protocols
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
PROFIDRIVE Standard Parameter
The following parameters defined by the PROFIBUS profile are realized in
the PROFIBUS module:
PNU
Explanation
918
Node address
927
Control sovereignty PIDV (always 1, i.e. PROFIBUS interface)
947
Error number:
The current error number is stored in this parameter.
965
Profile number (3.0)
967
Control word
968
Status word
970
Load data record
When the parameter is set to the value 1, a factory setting is made
and all change bits are set to 0.
971
Integration into the non-volatile memory
(is always done automatically)
Fig. 15-33: PROFIBUS module
These parameter numbers are not mapped.
Consistent Data Transmission
Usually, a PLC can only consistently transmit double words by I/O
memory access. With longer data formats (PIDV channel generally / PCD
with PPO2 or PPO4), system functions must be used (e.g. SFC14/15).