15-10
Control Communication - Field Busses and Protocols
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Bit
Valu
e
Significance
Notes
1
PCD valid
Valid process data is transmitted by the
master.
Note:
When only setpoint values are
transmitted via the bus (setting: interface),
this bit must be set to validate the
transmitted setpoint.
0
11
1
Clockwise
rotation
Clockwise rotation on
0
12
1
Counterclockwise
rotation
Counterclockwise rotation on
13
0/1
reserved
14
0/1
Parameter record
switching bit 0
00 parameter record 1
01 parameter record 2
10 parameter record 3
11 parameter record 4
15
0/1
Parameter record
switching bit 1
Fig. 15-13: Meaning of the bits in control word CTW
Summary of Contents for IndraDrive Fc FCS01