15-40
Control Communication - Field Busses and Protocols
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Code
Error description
Code
Error description
0
No error
6000
Device software
1000
General error
6310
Parameter loss
2200
Current within the device
7112
Overcurrent brake chopper
2310
Permanent overcurrent
output side
7120
Motor
3110
Mains overvoltage
7305
Incremental encoder 1
3120
Mains undervoltage
7300
Sensor
3130
Phase failure
7306
Incremental encoder 2
3210
Overvoltage within the
device
7310
Speed sensor
3230
Charging error
7320
Sensor position
4210
Overtemperature device
8100
Monitoring communication
4310
Overtemperature drive
8300
Torque loop
5110
Low-voltage supply
8400
Speed loop
5300
Operating panel
8612
Reference limit
5510
Data storage RAM
9000
External error
5520
Data storage Eprom
5530
Data storage EEPROM
Fig. 15-55: Error code
6040 control word
6041 status word
Bit
CanOpen significance
Bit
CanOpen significance
0
Activation
0
Ready for activation
1
Voltage disable
1
Activated
2
Quick stop
2
Operation enabled
3
Enable operation
3
Failure
4
Disable run-up encoder
4
Voltage disabled
5
Stop HLG
5
Quick stop
6
HLG zero
6
Activation disable
7
Error reset
7
Warning
8
Standstill
8
Actual value ok
9
Reserved
9
Remote
10
Reserved
10
Comparison value reached
11
Rotation direction
(0=clockwise)
11
Internal limit reached*
12
not used
12
0
13
not used
13
0
14
not used
14
Rotation direction
(0=clockwise)
15
not used
15
0
Fig. 15-56: Control word and status word
Object 603F error code
Object 6040 control word and
6041 status word
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......