11-20
Parameterization
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Parameter
Setting value / description / note
Device
Supervisor
Parameter
record
P403
Adjustment analog input 1
100%
S
-50.00 ...
50.00 V
[ 10.00 ]
This parameter is used to set the voltage corresponding to the maximum value of the
selected function of analog input 1. In factory setting (setpoint), this value corresponds to
the setpoint set via P105 Maximum frequency.
Typical setpoint values and corresponding settings.
0 – 10 V
10.00 V
2 – 10 V
10.00 V (monitored with the function 0-10V)
0 – 20 mA
5.00 V (internal resistance approx. 250
Ω
)
4 – 20 mA
5.00 V (internal resistance approx. 250
Ω
)
P400 ... P403
P401 = 0 0 – 10V limited
Sollwert P400-P403_a_de.fh11
Output
frequency
Setpoint value
voltage
P104
P105
P403
P402
0,0V
2,5V
5,0V
z.B.
10,0V
positive
P401 = 1 0 – 10V not limited
Sollwert P400-P403_b_de.fh11
Output
frequency
Setpoint value
voltage
P104
P105
0,0V
2,5V
5,0V
z.B.
10,0V
positive
negative
P403
P402
P404
Filter analog input 1
S
1 ... 400 ms
[ 100 ]
Settable digital low-pass filter for the analog signal. The spurious peaks are hidden and
reaction time extended.
P405
Function analog input 2
P
0 ... 82
[ 0 ]
Parameter P405 is identical with P400.
P406
Mode analog input 2
S
0 ... 3
[ 0 ]
This parameter is identical with P401.
P407
Adjustment analog input 2
0%
S
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......