15-26
Control Communication - Field Busses and Protocols
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
CANopen Protocol
Overview
Element
Description
Object directory
(OD)
The
OD
contains all objects of the device. Objects mirror the visible functionality.
They contain data, parameters or functions. They are accessed via
SDOs
. An
object is addressed via the
index
(16 bit) and the
sub-index
(8 bit). The OD is
subdivided into the following sections:
-
0000h...1FFFh: Communication-specific objects
-
2000h...5FFFh: Manufacturer-specific objects
-
6000h...9FFFh: Standardized device profile objects
-
A000h...FFFFh: reserved
Service Data
Obj.
(SDO)
Via
SDOs
, confirmed transfer of data of any length between two nodes takes
place: Here, the
SDO client
is the initiating node and has direct access to the OD
entries of the
SDO server
(read or write). Usually, the SDO transfer is used for
parameterization and for service purposes.
Process Data
Obj.
(PDO)
PDOs
are used to transmit process data. The process data can comprise 8 byte as
a maximum. They are transmitted unconfirmed. The significance of the
transmitted data is specified by the identifier and the set
PDO mapping
. A PDO
generally has one producer (sender). It can have several consumers (receivers),
however.
PDO mapping
In the objects 1600h-1603h or 1A00h..1A03h, it can be specified which objects
(setpoint/actual values) are transmitted in the PDO telegrams.
Each CAN message has an 11 bit identifier. Via this identifier, addressing and priority
allocation take place.
CANopen defines a preset identifier allocation which provides for communication between
an upstream device with up to 127 other devices. The 11 bit identifier is divided as follows:
10
9
8
7
6
5
4
3
2
1
0
Function code
Node identifier (0[all], 1-127)
Object
Function code
Resulting COB-ID
Index OD entry
NMT
0000
0
SYNC
0001
80h
1005h-1007h
Time stamp
0010
100h
1012h, 1013h
Emergency
0001
81h – FFh
1014h, 1015h
PDO1 (Tx)
0011
181h – 1FFh
1800h, 1A00h
PDO1 (Rx)
0100
201h – 27Fh
1400h, 1600h
PDO2 (Tx)
0101
281h – 2FFh
1801h, 1A01h
PDO2 (Rx)
0110
301h – 37Fh
1401h, 1601h
PDO3 (Tx)
0111
381h – 3FFh
1802h, 1A02h
PDO3 (Rx)
1000
401h – 47Fh
1403h, 1602h
PDO4 (Tx)
1001
481h – 4FFh
1803h, 1A03h
PDO4 (Rx)
1010
501h – 57Fh
1403h, 1603h
SDO (Tx)
1011
581h – 5FFh
1200h
SDO (Rx)
1100
601h – 67Fh
1200h
Identifier
NMT Error Control
1110
701h – 77Fh
1016h, 1017h
Fig. 15-34: Protocol elements
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......