Rexroth IndraDrive FCS01.1
Parameterization
11-15
DOK-INDRV*--FCS01*****-IB01_EN-P
P215
Rate-action boost
S
P
0 ... 200 %
[ 0 ]
Only with linear characteristic (P211 = 0% und P212 = 0%).
For drives requiring high startup torque, this parameter offers the option to supply an
additionally current during the startup phase. The duration is limited; it can be selected in
parameter >Time rate-action boost< P216.
P216
Time rate-action boost
S
P
0.0 ... 10.0 s
[ 0 ]
Only with linear characteristic (P211 = 0% und P212 = 0%).
Duration for which the increased startup current is effective (P115).
P2xx
Control parameter
P211
P210
P204
P201
P216
P215
Output
voltage
Output frequency
Duration
Note:
"typical" setting for the …
Current vector control
(factory setting)
P201 to P208 = Motor data
P210 = 100%
P211 = 100%
P212 = 100%
P213 = 100%
P214 = 0%
P215 = insignificant
P216 = insignificant
Linear U/f characteristic
P201 to P208 = Motor data
P210 = 100% (static boost)
P211 = 0%
P212 = 0%
P213 = 100% (insignificant)
P214 = 0% (insignificant)
P215 = 0% (dynamic boost)
P216 = 0s (duration dyn. boost)