Parameter
Setting value / description / note
Device
Supervisor
Parameter record
P537
Pulse deactivation
S
10...200%/201
[ 150 ]
This function is used to prevent quick deactivation of the FC when a corresponding load is
applied. With pulse deactivation activated, the output current is limited to the set value.
This limitation is realized by temporary deactivation of individual output transistors. The
current output frequency is retained.
10...200% = limit value in respect of the nominal FC current
201% = function is deactivated
Note:
A smaller value in P536 may fall below the value set here.
With small output frequencies (< 4.5 Hz) or high pulse frequencies (> 6 kHz),
the power reduction (also see Chapter 13.2, Derating of Electrical Data) may
fall below the pulse deactivation.
Note:
When pulse deactivation is switched off (P537=201) and a high pulse
frequency is selected in parameter P504, the frequency converter will
automatically reduce the pulse frequency on reaching of power limits.
When the frequency converter is relieved again, the pulse frequency
will return to its original higher value.
P538
Monitoring of mains
voltage
S
0 ... 4
[ 3 ]
For safe operation of the frequency converter, the power supply must meet certain quality
criteria. If a phase is temporarily interrupted, or if the supply voltage falls below a certain
limit, the converter will signal a failure.
Under certain circumstances, it may be necessary to suppress this error message. In this
case, input monitoring can be adjusted.
0 =
Switched off:
no monitoring of the supply voltage.
1 =
Only phase error:
only phase errors cause an error message.
2 =
Only undervoltage:
only undervoltages cause an error message.
3 =
Phase error and undervoltage:
undervoltages and phase errors cause an error
message.
4 =
DC supply:
In case of direct supply with DC voltage the input voltage is fixedly
received at 480 V. Phase error and mains undervoltage monitoring is deactivated.
Note:
The FC may be destroyed if operated with an impermissible mains voltage!
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......