11-24
Parameterization
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Parameter
Setting value / description / note
Device
Supervisor
Parameter
record
15 =
External brake
16 =
Converter is running
17 =
Current limit
18 =
Torque current limit
19 =
Frequency limit
20 =
Setpoint value reached
21 =
Failure
22 =
Warning
23 =
Overcurrent warning
24 =
Overtemperature warning motor
25 =
Torque current limit active
26 =
Value of P541, external control
27 =
Regenerative torque current limit
28 =
... 29
reserved
34 =
... 43
reserved
44 =
Bus in bit 0
45 =
Bus in bit 1
46 =
Bus in bit 2
47 =
Bus in bit 3
48 =
Bus in bit 4
49 =
Bus in bit 5
50 =
Bus in bit 6
51 =
Bus in bit 7
52 =
Output via bus
P419
Scaling of analog output
P
-500 ... 500 %
[ 100 ]
analog functions P418 (= 0…14, 30, 31)
This parameter is used to adjust analog output to the desired operation range. The
maximum analog output (10V) corresponds to the scaling value of the respective selection.
With a constant operating point, it follows that if this parameter is increased from 100% to
200%, the analog output voltage is reduced by half. Then, 10 volt output signal
correspond to double the nominal value.
With negative values, the logic is reversed. Then, a setpoint value of 0% is rendered at the
output with 10V, and -100% with 0V.
digital functions P418 (= 15…27, 44… 52)
With the function current limit (= 17), torque current limit (= 18) and frequency limit (=
19), this parameter can be used to set the switching threshold. The 100% value refers to
the corresponding nominal motor value (also see P435).
With a negative value, the output function is rendered negativated (0/1
→
1/0).
P420
Function digital input 1
0 ... 62
[ 1 ]
Release right
as factory setting
Various functions may be programmed. Please refer to the following table.
P421
Function digital input 2
0 ... 62
[ 2 ]
Release left
as factory setting
Various functions may be programmed. Please refer to the following table.
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......