11-26
Parameterization
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
List of potential functions of the digital inputs P420…P424
Value
Function
Description
Signal
00
no function
Input is switched off.
---
01
Release right
FC supplies the output signal, phase sequence right
(with positive setpoint value) 0
→
1 edge (P428 = 0)
high
02
Release left
FC supplies the output signal, phase sequence left (with
positive setpoint value) 0
→
1 edge (P428 = 0)
high
If automatic startup is active (P428 = 1), a high level is sufficient. If the functions 'release right'
and 'release left' are addressed simultaneously, the FC will be blocked.
03
Reversal of
rotation direction
Results in reversal of phase sequence in connection
with release right or left
high
04
Fixed frequency 1
)
The frequency of P429 is added to the current setpoint
value.
high
05
Fixed frequency 2
1)
The frequency of P430 is added to the current setpoint
value.
high
06
Fixed frequency 3
1)
The frequency of P431 is added to the current setpoint
value.
high
07
Fixed frequency 4
1)
The frequency of P432 is added to the current setpoint
value.
high
If several fixed frequencies are addressed simultaneously, they are added with the right signs.
Furthermore, the analog setpoint value (P400) and if applicable the minimum frequency (P104)
are added.
08
Switch of
parameter record
bit 0
Selection of the active parameter record 1…4 (100)
high
09
Hold frequency
During startup or braking phase, a low level caused a
"holding" of the current output frequency. A high level
allows the ramp to continue.
low
10
Block voltage
2)
The FC output voltage is switched off, the motor runs
down freely
low
11
Quick stop
2)
The FC reduces the frequency with the programmed
quick stop time of P426.
low
12
Confirmation of
failure
2)
Confirmation of failure with an external signal.
0
→
1
edge
13
PTC thermistor
input
2)
Analog evaluation of the applied signal. Switching
threshold approx. 2.5 volt. Switch-off delay = 2sec,
warning after 1 sec.
analog
14
Remote control
2)
With control via bus system, the system switches to
control via control terminals in case of low level.
high
15
Jog frequency
1)
Fixed frequency value that can be set via the UP /
Down and the ENTER keys (P113).
high
16
Hold frequency
motor
potentiometer
Same as setting value 09, but below minimum
frequency P104 and above max. frequency P105, the
frequency is not held.
low
17
Parameter record
switch bit 1
Selection of the active parameter record 1…4 (100)
high
18
Watchdog
2)
The input must cyclically (P460) see a high edge;
otherwise, the system switches off with error E012.l The
function starts with the 1. high edge.
0
→
1
edge
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......