Rexroth IndraDrive FCS01.1
Installation
8-13
DOK-INDRV*--FCS01*****-IB01_EN-P
X31, Relay 1 (1, 2), Relay 2 (3, 4)
Adjust the function of this relay according to your requirements with the
parameters P434 through P443. They may be operated with max. 230V
AC/24V DC, 2A.
In factory setting, the closed contact signals the frequency converter's
readiness for operation at the terminals 3-4 (relay 2). When an error
message is pending or when the frequency converter is de-energized, the
contact is open.
The terminals 1-2 (relay 1) can control a mechanical motor brake in
factory setting. Only in this way, it releases and is applied again at the
right moment. To optimize the temporal sequence, set the respective
delay (0.2 - 0.3 s) in parameter P107.
Fig. 8-14:
Relay connection
X5, Connection of Motor Cable (PE, U, V, W)
The motor cable can have a
total length of 100 m
if it is a standard
unshielded type. If you use a shielded cable run the cable in a well-
grounded metallic cable duct, the
total length
should not exceed
30 m
.
With greater cable lengths , use an additional output throttle (accessory)..
Note:
Please also take note of Chapter 13.4, Electromagnetic
Compatibility (EMC).
Note:
For operation with several motors, the total motor cable length
is the sum of all individual cable lengths.
Fig. 8-15:
Motor cable
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......