Rexroth IndraDrive FCS01.1
Control Communication - Field Busses and Protocols
15-53
DOK-INDRV*--FCS01*****-IB01_EN-P
Details:
Precondition (status word of the converter)
Byte no.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Significance
STX
LG
ADR
PID
PID
IND
IND
PV
PV
STW
STW
AV1
AV1
BCC
hexadecimal
02
0C
0A
00
00
00
00
00
00
0B
31
00
00
37
Fig. 15-71: Status word of the converter
The following telegram must be sent to the converter:
Byte no.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Significance
STX
LG
ADR
PID
PID
IND
IND
PV
PV
CTW
CTW
SP1
SP1
BCC
hexadecimal
02
0C
0A
00
00
00
00
00
00
04
7F
20
00
5F
Fig. 15-72: Example: Status word transmission telegram
The converter accelerates the motor at the ramp. When the converter has
reached 50% setpoint value, it will respond by transmitting the following
telegram:
Byte no.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Significance
STX
LG
ADR
PID
PID
IND
IND
PV
PV
STW
STW
AV1
AV1
BCC
hexadecimal
02
0C
0A
00
00
00
00
00
00
0F
37
20
00
1C
Fig. 15-73: Example: Status word response telegram
Note:
In bit 10 of the response telegram, the status of MFR 1 is
signaled. Depending on the programmed function and state,
the status word may change.
Writing a Parameter
When transmitting parameter jobs, please note that the slave will not
directly respond to the job in the parameter channel of the master
telegram but that the positive response may be delayed by one or several
communication cycles. For this reason, the master must repeat the
requested job until it has received the corresponding response from the
slave.
The run-up time parameter (USS no. = 102
dez
/ 66
hex
) of a frequency
converter with the USIP address 3 should be set to the value 10sec in
parameter record 3. There aren't any process data transmitted.
As the run-up time has a converter-internal resolution of 0.01s, a
parameter value of 10 / 0.01 = 1000 (3E8
hex
) must be transmitted for a
period of 10sec. PPO1 is selected as PPO type.
Procedure:
•
Set address (address 03)
•
Select parameter (P 102
dez
/ P 66
hex
)
•
Select job identification (2 = change parameter value (word))
•
Select parameter record 2 (IND = 01)
•
Set parameter value (1000
dez
/ 3E8
HEX
)
•
Transmit
telegram
•
Check response telegram
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......