Preset Values - Activation of DeviceNet
To operate the converter with the DeviceNet protocol, the bus must be
connected to the master, and a number of settings must be made at the
converter.
With the DeviceNet protocol, the converter parameters are mapped to
DeviceNet objects in the range 100 to 107.
Computation
Class
100 + parameter number / 100
Attribute
Parameter number % 100
Instance
Su1
Parameter number
(Class – 100) * 100 + attribute
SubIndex
Instance -1
Fig. 15-83: Preset Values - Activation of DeviceNet
The converter can be parameterized at all times. Control of the converter
via DeviceNet can be activated by setting the parameter
P509
to the
value 7.
Note:
After activation, the functions
Block voltage, quick-stop,
remote control
, and
error confirmation
are generally
available at the control terminals (locally). To operate the
drive, a high signal must be applied at the used digital inputs
before the drive can be released.