11-40
Parameterization
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Parameter
Setting value / description / note
Device
Supervisor
Parameter record
P539
Output monitoring
S
P
0 ... 3
[ 0 ]
This safety function is used to monitor the output current at the terminals U-V-W and to
check it for plausibility. In case of failure, error message E016 is output.
0 =
Switched off:
No monitoring takes place.
1 =
Only motor phase error:
The output current is measured and checked for
symmetry. If there is an asymmetry, the FC will switch off and signals error E016.
2 =
Only magnetization monitoring:
In the moment of FC activation, the amount
of magnetization current (field current) is checked. If there is not enough
magnetization current, the FC will switch off with error message E016. This
happens independent of the parameters P107/P114; no motor brake is released.
3 =
Motor phase and magnetization monitoring
Note:
This function is recommended as an additional safety function for lifting gear
applications, but is impermissible as a sole measure for protection of
individuals.
P540
Rotation direction mode
S
P
0 ... 7
[ 0 ]
This parameter can be used to prevent for safety reasons a reversal of rotation direction,
and thus incorrect rotation.
0 =
No limitation of the rotation direction
1 =
Block reversal of rotation direction;
the rotation direction key of the comfort
control panel is blocked.
2 =
Only clockwise rotation
*
; only phase sequence right is possible. Selection of
the "incorrect" sense of rotation results in output of 0Hz.
3 =
Only anti-clockwise rotation
*
; only phase sequence left is possible. Selection
of the "incorrect" sense of rotation results in output of 0Hz.
4 =
Only release direction;
sense of rotation is possible only in accordance with the
release signal; otherwise, 0Hz is supplied.
5 =
Only clockwise rotation monitored
*
; only phase sequence right is possible.
Selection of the "incorrect" sense of rotation results in FC deactivation.
6 =
Only anti-clockwise rotation monitoring
*
; only phase sequence left is
possible. Selection of the "incorrect" sense of rotation results in FC deactivation.
7 =
Only release direction monitored;
sense of rotation is only possible according
to the release signal; otherwise, the FC is deactivated.
*) is applicable for control via keyboard and control terminals,
and the direction key of the standard control panel is blocked.
P541
Set relay
S
0000 ... 3F1F
(hex)
[ 0000 ]
This function offers the possibility to control the relays and the digital outputs independent
of the frequency converter status. To this end, the output in question must be set to the
function "external control".
This function can be used manually or in connection with a bus address.
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......