2-6
Safety Instructions for Electric Drives and Controls
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
⇒
With electrical drive and filter components, observe
the following:
Wait 30 minutes after switching off power to allow
capacitors to discharge before beginning to work.
Measure the voltage on the capacitors before
beginning to work to make sure that the equipment is
safe to touch.
⇒
Never touch the electrical connection points of a
component while power is turned on.
⇒
Install the covers and guards provided with the
equipment properly before switching the device on.
Before switching the equipment on, cover and
safeguard live parts safely to prevent contact with
those parts.
⇒
A residual-current-operated circuit-breaker or r.c.d.
cannot be used for electric drives! Indirect contact
must be prevented by other means, for example, by
an overcurrent protective device according to the
relevant standards.
⇒
Secure built-in devices from direct touching of
electrical parts by providing an external housing, for
example a control cabinet.
European countries: according to EN 50178/ 1998,
section 5.3.2.3
.
USA: See National Electrical Code (NEC), National
Electrical Manufacturers' Association (NEMA), as well as
local engineering regulations. The operator must observe
all the above regulations at any time.
With electrical drive and filter components, observe the following:
DANGER
High housing voltage and large leakage current!
Risk of death or bodily injury by electric shock!
⇒
Before switching on, the housings of all electrical
equipment and motors must be connected or
grounded with the equipment grounding conductor to
the grounding points. This is also applicable before
short tests.
⇒
The equipment grounding conductor of the electrical
equipment and the units must be non-detachably
and permanently connected to the power supply unit
at all times. The leakage current is greater than
3.5 mA.
⇒
Over the total length, use copper wire of a cross
section of a minimum of 10 mm
2
for this equipment
grounding connection!
⇒
Before start-up, also in trial runs, always attach the
equipment grounding conductor or connect with the
ground wire. Otherwise, high voltages may occur at
the housing causing electric shock.
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......