4-79
H
Parameters Requiring Setting
Parameter No.
Parameter name
Explanation
Reference
Pn50F.2
Output signal
selection 2: BKIR
signal selection
Be sure to allocate BKIR.
(See note.)
4-4-3 Important
Parameters
Pn506
Brake timing 1
This parameter sets the BKIR
output timing.
P 506 S t l
ti
f
4-4-4 Parameter Details
Pn507
Brake command
speed
Pn506: Sets lag time from
BKIR OFF to servo OFF.
Pn507: Sets the rotation
speed for turning BKIR OFF.
Pn508
Brake timing 2
speed for turning BKIR OFF.
Pn508: Sets the standby time
from servo OFF to BKIR OFF.
Note
BKIR is not allocated in the default settings.
H
Operation
D
RUN Timing (When Servomotor Is Stopped)
RUN
BKIR (brake interlock)
Brake power
supply
Brake operation
Speed command or
pulse command
Servomotor energizing
200 ms max.
Approx. 2 ms
100 ms max.
Pn506 (See note 2.)
0 to 35 ms
See note 1.
Deenergized
Energized
Note 1.
The time from turning ON the brake power supply to the brake being released is 200 ms max.
Set the speed command (pulse command) to be given after the brake has been released,
taking this delay into account.
Note 2.
The time from turning OFF the brake power supply to the brake engaging is 100 ms max. If
using the Servomotor on a vertical axis, set Pn506 (brake timing 1) so that the Servomotor
deenergizes after the brake has engaged, taking this delay into account.
Operation
Chapter 4