4-28
Para-
meter
No.
Restart
power?
Setting
range
Unit
Default
setting
400 V
Default
setting
100/200 V
Explanation (See note 1.)
Parameter
name
Para-
meter
No.
Restart
power?
Setting
range
Unit
Default
setting
400 V
Default
setting
100/200 V
Explanation (See note 2.)
Set-
ting
Name
Digit
No.
Parameter
name
Pn50b
Input
signal
selection 2
0
NOT
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
NOT (reverse drive
prohibited) signal allocation
6548
6543
---
---
Yes
1
RESET
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
RESET (alarm reset) signal
allocation
2
PCL
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
PCL (forward rotation
current limit) signal
allocation
3
NCL
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
NCL (reverse rotation
current limit) allocation
Pn50C Input
signal
selection 3
0
RDIR
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
RDIR (rotation direction
command) signal allocation
8888
8888
---
---
Yes
1
SPD1
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
SPD1 (speed selection
reference 1) signal
allocation
2
SPD2
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
SPD2 (speed selection
command 2) signal
allocation
3
TVSEL
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
TVSEL (control mode
switching) signal allocation
Pn50d
Input
signal
selection 4
0
PLOCK
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
PLOCK (position lock
command) signal allocation
8888
8888
---
---
Yes
1
IPG
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
IPG (pulse disable) signal
allocation
2
GSEL
signal
Input
terminal
allocation
0 to
F
Same as Pn50A.1.
GSEL (gain switching)
signal allocation
3
Not used. 0
(Do not change setting.)
Operation
Chapter 4