4-106
•
Set the measured frequency using Pn409 (notch filter frequency).
•
Adjust the value of Pn409 slightly to minimize output torque vibration.
•
When the vibration is minimal, adjust Pn100 (speed loop gain), Pn101 (speed loop integration con-
stant), Pn102 (position loop gain), and Pn401 (torque command filter time constant) once again, ac-
cording to
4-7-2 Manual Tuning
.
4-8-7
Speed Feedback Compensation (Position, Speed,
Internally-set Time Control)
H
Functions
•
This function shortens positioning time.
•
This function works to lower the speed loop feedback gain, and raise the speed loop gain and position
loop gain. Consequently, responsiveness to commands is improved, and positioning time can be
shortened. Noise sensitivity is lowered, however, so positioning time cannot be shortened where there
is external force applied, such as with the vertical axis.
Note
If you use the speed feedback compensation function, online auto-tuning will not operate normal-
ly. To use the speed feedback compensation function, turn OFF the online auto-tuning (Pn110.0 =
2).
H
Parameters Requiring Settings
Parameter No.
Parameter name
Explanation
Reference
Pn110.1
Selects speed
feedback
compensation
function
To use the speed feedback compensation function,
set Pn110.1 to 1 (speed feedback compensation
function ON).
4-4-4
Parameter
Details
Pn111
Speed feedback
compensating gain
Adjusts the speed loop feedback gain.
•
Reduce the setting value for Pn111 (speed feedback compensating gain) to increase the speed loop
gain and position loop gain. If the value is too small, the response may vibrate.
H
Setting Procedure
•
To perform adjustment, measure the position error and torque command. Refer to the OMNUC W-se-
ries Servo Driver personal computer monitoring software to measure the analog monitor output.
•
Follow
4-7-2 Manual Tuning
to adjust Pn100 (speed loop gain), Pn101 (speed loop integration time
constant), Pn102 (position loop gain), and Pn401 (torque command filter time constant) to quickly set
the position error to zero without the torque command vibrating.
•
After completing tuning, lower Pn111 to 10, and adjust Pn100, Pn101, Pn102, and Pn401 in the same
way.
Operation
Chapter 4
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]