4-63
Pn510
Output signal selection 3 (All
operation modes)
Default
setting
0000
Restart
power?
Yes
Pn512
Output signal reverse (All operation
modes)
Default
setting
0000
Restart
power?
Yes
Note
Refer to
4-4-3 Important Parameters
.
Pn511
Not used.
Setting
range
---
Unit
---
Default
setting
8888
Restart
power?
No
Note
Do not change the setting.
H
Other Parameters (From Pn600)
Pn600
Regeneration resistor capacity
Setting
range
0 to Unit
type
Unit
x 10 W
Default
setting
0
Restart
power?
No
•
If using an External Regeneration Resistor or External Regeneration Resistance Unit, set the regen-
eration absorption amount. Set the regeneration absorption amount for when the temperature rises
above 120
°
C, not the nominal amount. (Refer to
Regenerative Energy Absorption Using External Re-
generation Resistance
for details.)
•
Perform Un00A (regeneration load monitor) calculations, and A.92 (regeneration overload warning)
and A.32 (regeneration overload alarm) based on the Pn600 setting.
Note
If an External Regeneration Resistor or External Regeneration Resistance Unit is not connected,
set Pn600 to 0.
Pn601
Not used.
Setting
range
---
Unit
---
Default
setting
0
Restart
power?
No
Note
Do not change the setting.
Operation
Chapter 4