10-1 Controller
Link
Network Diagnostic Tool
10-1-2 Diagnosing
Network
Status
10-8
Correct the network so that there are no more than two hierarchies using
T-branches, and then restart the Diagnostic Tool. For details, refer to the
Controller
Link Repeater Unit Operation Manual
.
•
The background of the node icon will be displayed in red when there are errors in a
Controller Link Unit or CPU Unit.
•
Information on errors at nodes will be displayed in the diagnosis results area.
•
Errors shown in the diagnosis results area can be double-clicked to display details on
the error. (Details on the error can also be displayed by double-clicking node icons
with red backgrounds.)
Note
Errors shown in the diagnosis results area can be double-clicked to display details on
the error. When this is done, the contents of the Auxiliary Area or AR and SR Areas
are automatically read from the CPU Unit and stored in a file. The file is stored as
required in a log file in the folder where the CX-Integrator is installed. The file is in CSV
(text) format.
File names consist of the node address and the time from the PLC.
PLC model
Read area
CS Series
Auxiliary Area, A000 to A959
CJ Series
Auxiliary Area, A000 to A959
CVM1/CV Series
Auxiliary Area, A000 to A511
C200HX/HG/HE
AR Area, AR 00 to AR 27
SR Area, SR 236 to SR 289
CQM1H Series
AR Area, AR 00 to AR 27
SR Area, SR 190 to SR 243
Computers (or NS-series
Programmable Terminals,
Open Network Controllers,
etc.)
Cannot be read.
The Auxiliary Area and AR/SR Areas contain details on error status, the time when the
power was turned ON to the PLC, etc. This file can be used later for analysis.
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......