3-1 Routing Table Overview
3-1-6 Operating Procedures Prior to Routing Table Transfer
3-9
Creating the FINS Local Routing Tables Offline
Select the destination network and node.
In the Connecting PLC Change Dialog Box, select the Communications
Unit that connects to the network and the node address.
Connect online with the PLC that is directly connected to the CX-Integrator (making it the target PLC).
Select
Network – Auto Online
or
Network – Work Online
from the CX-Integrator's menu bar.
Transfer the routing tables to the PLC (from the computer to the target PLC).
Select
Options – Transfer to PLC
from the PLC routing table menu.
Create the FINS local routing tables (in the PLC routing tables).
Create the local network table.
Create the relay network table.
Save the created routing tables.
Select
File – Save Local Routing Table File
from the PLC routing table's menu.
Check the routing tables for errors.
Select
Options – Check Routing Table for errors
from the PLC routing table's menu.
Start the Routing Table Component. (Start the PLC routing tables.)
Select
Tools – Start Routing Table
from the CX-Integrator's menu bar.
Set the gateway counter. (CS/CJ-series CPU Units must be unit version 3.0 or later.)
Click the
SIOU
Tab when the PLC routing table is displayed, right-click the local PLC's icon, and select
Set Gateway Counter
from the menu.
Update the display in the Online Connection Information Window.
In the Online Connection Information Window, select
View – Update of Online Information Window
.
Note: Use one of the following PLC models as the PLC
directly connected by serial communications.
•
A CS/CJ-series CPU Unit with unit version 4.0 or later
Transferring to a PLC with a direct serial connection
Transferring to a node in the network through the directly
connected PLC. (See note.)
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......