3-2 Setting the Routing Tables
3-2-3 Setting the Gateway Counter
3-21
Setting the Gateway Counter in a FINS Network Routing Table:
1. Click the
Network
Tab at the bottom of the PLC Routing Table Window, right-click
the icon of a PLC in the network, and select
Set Gateway Counter
.
2. The Gateway Counter Setting Dialog Box will be displayed.
Select
Standard
or
Expand
and click the
OK
Button.
Standard: Up to 3 level crossings (GCT = 02 hex)
Expand: Allows 4 to 8 level crossings (GCT = 07 hex)
The gateway counter value is displayed in the Main View, Overview, and Table
View windows.
Main View
Overview
Table View
CS/CJ-series Units Version 2.0
The GCT (gateway counter) is fixed at 07 Hex. The GCT cannot be set for a maximum
of 3 network layer crossings. The maximum number of network crossings is always 8
layers max.
When CX-Programmer version 5.0 or a later version is being used, the
Standard/Expand
setting in the Gateway Counter Setting Dialog Box is ignored. When
the routing tables are transferred to a Version 2.0 CS/CJ-series Unit, the GCT value is
always set to 07 Hex and operates in Expand Mode.
Pre-Version 2.0 CS/CJ-series Units
The GCT (gateway counter) is fixed at 02 Hex. In this case, the maximum number of
network crossings is always 3 layers max.
When CX-Programmer version 5.0 or a later version is being used, the setting in the
Gateway Counter Setting Dialog Box is ignored and the
Standard
setting is always
selected. If the
Expand
setting has been set, the routing tables cannot be transferred.
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......