7-6 Editing Master Unit Parameters
7-6-3 Editing the Software Setting Table
7-26
7-6-3
Editing the Software Setting Table
The CompoNet Master Unit has 5 communications modes. When using
communications modes 0 to 3, the CompoNet Unit IN/OUT information is allocated
in the Special I/O Unit Area. When using communications mode 8 (Software Setting
Mode), the CompoNet Unit IN/OUT information can be allocated in the CIO, DM,
WR, and HR Areas, in addition to the Special I/O Unit Area.
The Software Setting Table is used in the following situations.
•
When allocating words in an area other than the Special I/O Unit Area to Slave
Units
•
When setting the number of words allocated, e.g., when words after those
allocated to the Slave Units will be used for another purpose.
In the Software Setting Mode, memory is allocated to each Word Unit and Bit Unit
for the Word IN/OUT Areas, Bit IN/OUT Areas, Participation Flags, and
Communications Error Flags.
CX-Integrator
Word Slaves
CompoNet
Bit Slaves
CompoNet Master Unit
CS/CJ-series PLC
The addresses and areas for the Word OUT
Area, Word IN Area, Bit OUT Area, Bit IN Area,
Participation Flags, and Communications Error
Flags are set for each Word Unit and Bit Unit.
Software Setting Table
Area
Start
area/address
Number
of nodes
Word OUT
Word IN
Bit OUT
Bit IN
Participation/Communications
Error Flags: Word Units
Participation/Communications
Error Flags: Bit Units
I/O memory
Mode No. = 8
Word IN Area
Word OUT Area
Word Unit Participation
Status
Bit IN Area
Bit OUT area
Bit Participation Status
User-set location
→
User-set location
→
User-set location
→
User-set location
→
User-set location
→
User-set location
→
:
:
1. Set the communications mode to No. 8 (see note) by using the rotary switch on
the front of the Master Unit.
Note:
The Software Setting cannot be set in any communications mode other than No. 8.
2. Turn ON the CompoNet Unit and computer.
3. Start the CX-Integrator, create the I/O tables, and then connect online to the
CompoNet Network.
4. Right-click the
Master Unit
Icon in the Network Configuration Window and
select
Parameter - Edit
. The Master Unit’s Parameter Dialog Box will be
displayed.
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......