2-2
Connecting Online to the Relay PLC
2-2-2 Procedures
2-18
Field name on
Driver Tab Page
Contents
Settings
Selected
(default).
The node number (node address) is
automatically created based on the IP
address of the computer. The node
number on the left will be grayed out
and the node number will be the
least-significant digit of the IP address of
the computer at that time.
Auto-detect
Selection
cleared.
Clear this selection to enable using an
IP address table or combined method.
The workstation node address on the
left can be input when the selection is
cleared.
Workstation Node
Number
The node address of the computer is
set when the
Auto-detect
selection is
cleared (IP address table or combined
method).
1 to 254
IP Address
Set the IP address of the connected
Ethernet Unit.
Note: The IP address setting method
and default depends on the
model of Ethernet Unit being
used. Refer to the operation
manual of the Ethernet Unit for
details.
Default IP address for the
CS1W-ETN21/CJ1W-ETN21 Ethernet
Unit:
192.168.250.
FINS_node_address
Port Number
Set the UDP port number. Normally,
the default value of 9600 should be
used.
1 to 65535
Default: 9600
Setting the IP Address Table at the CX-Integrator (Computer)
When Ethernet is selected as the network type in the communications settings, and the
IP conversion for any node on Ethernet (i.e., an Ethernet Unit or personal computer) is
set for either the IP address table method or the combined method, the IP address table
at the CX-Integrator (personal computer) must be preset. (For details on IP conversion,
refer to the
Ethernet Units Construction of Networks Operation Manual
.)
1. Select
Communication Settings
from the Network Menu.
2. The Change PLC Dialog Box will be displayed.
3. Select Ethernet as the network type, and click the
Settings
Button. The Network
Settings [Ethernet] Dialog Box will be displayed.
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......