1-2 Specifications
1-2-1 CX-Integrator
Specifications
1-9
Item
Specification
Either of the following can be used.
Serial
communications
Direction connection is possible to any of the following serial ports on a
CS/CJ/CP-series PLC.
•
CPU Unit USB port (Toolbus)
•
CPU Unit peripheral port (Toolbus or Host Link)
•
CPU Unit RS-232C port (Toolbus or Host Link)
•
A CP-series CPU Unit is connected to the USB port using a
commercially available USB cable (type B – type A).
•
Serial Communications Board or Serial Communications Unit RS-232C
port or RS-422A/485 port (Host Link) (See note.)
Note: For a CP-series CPU Unit, connect to a CP1W-CIF01/11 Option
Board (Toolbus or Host Link).
Direct connection is possible to any of the following serial ports on an
NSJ-series NSJ Controller.
•
RS-232C port A (Toolbus) on NSJ Controller
•
RS-232C port B (Toolbus) on NSJ Controller
•
USB port on NSJ Controller
Note: Automatic online connection is possible for serial communications
ports. (The user does not have to set the computer communications
settings.) The communications settings will be automatically set to
those of the PLC. Connection is possible to a serial port on the CPU
Unit, a Serial Communications Board, or a Serial Communications
Unit. For PLC serial ports, however, only the Toolbus or Host Link
serial communications modes can be used and the baud rate must
be 9600, 19200, 38400, or 115200 bits/s.
Connecting to the
Relay PLC
FINS network
communications
Direction connection is possible through any of the following networks on
a CS/CJ-series PLC or NSJ-series NSJ Controller.
•
Ethernet (Ethernet, Ethernet FINS/TCP, or FinsGateway (See note.))
•
Controller Link (Controller Link or FinsGateway (See note.))
•
SYSMAC LINK (SYSMAC LINK or FinsGateway (See note.))
Note:
If FinsGateway is selected, connection will not be possible to a DeviceNet, CompoNet,
or CompoWay/F network. To connect to any of these networks, use Ethernet, Ethernet
(FINS/TCP), Controller Link, or SYSMAC LINK instead of FinsGateway.
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......