2-8
Comparing Network Configurations
2-8-1 Overview
2-54
2-8
Comparing Network Configurations
2-8-1 Overview
The configuration of a virtual network on the computer can be compared to the
configuration of an actual network. The model numbers of all nodes are also compared.
Component parameters are not compared.
Computer running
CX-Integrator
Network Configuration Window
CS/CJ-series PLC
Target PLC
Relay PLC
CompoWay/F
Temperature
Controller
Smart Sensor
Results of
comparison
(Node model numbers are also compared.)
Structure compared
2-8-2 Procedure
1. Right a network in the Workspace Window and select
Connect
from the pop-up
menu. Accessing the network will be enabled and the icon to the left will change to
.
If the network has been uploaded but a network address is not displayed (Net(-)
displayed), it will be necessary to select the desired network in the Workspace
Window, right-click, and select
Connect.
2. Right-click the network and select
Compare
from the pop-up menu.
For an Ethernet network, the following dialog box will be displayed.
Check to confirm that no nodes other than OMRON Ethernet Units or FinsGateway
exist in the same segment, and then click the
OK
Button.
!
Caution
Do not use this function if a node exists for something other than an OMRON
Ethernet Unit or FinsGateway within the same segment on Ethernet, and when the
Ethernet network system is in operation. When an Ethernet network configuration
upload is executed, an OMRON FINS command is sent to all nodes in the segment.
Therefore, if a node exists for something other than an OMRON Ethernet Unit or
FinsGateway, the FINS command will not be received at that node and unexpected
operation may occur.
3. The network configuration of the virtual network will be compared to the configuration
of the network with the same network address and the results will be displayed.
Note:
The virtual networks on the computer correspond to actual networks with the same network
addresses.
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......