7-6 Editing Master Unit Parameters
7-6-2 Editing the Registration Table
7-25
Setting the Slave Active Timer and Enabling Waiting for All Slaves
The Slave Active Timer and Enable Waiting All Slave Active Function are set to control
operation when a slave joins the network. The Slave Active Timer, Enable Waiting All
Slave Active Function, and Registration Table Check Type are set as follows:
1. Turn ON the REGS switch on the front of the Master Unit.
2. Turn ON the CompoNet Unit and computer.
3. Start the CX-Integrator and connect online.
4. Right-click the
Master Unit
Icon in the Network Configuration Window and
select
Parameter - Edit
. The Master Unit’s Parameter Dialog Box will be
displayed.
5. Select the
Edit the Registration Table
Check Box on the General Tab Page.
The Registration Table Tab Page will be displayed.
6. Click the
Advanced Setting
Button. The Advanced Setting Dialog Box will be
displayed.
7. Adjust the settings.
For information on settings, refer to the Registration Table Tab Page in
7-6-1
Master Unit Parameter Settings
.
8. Click the
OK
Button. The Advanced Setting Dialog Box will close.
9. Click the
OK
Button. The settings will be saved.
Summary of Contents for CJ Series
Page 2: ......
Page 3: ...CXONE AL C V3 CXONE AL D V3 CX Integrator Ver 2 3 Operation Manual Revised February 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 18: ...xviii ...
Page 154: ...Communications Section 3 Routing Tables This section describes how to set the routing tables ...
Page 189: ...3 3 Maintenance after Network Configuration 3 3 2 Editing the FINS Local Network Tables 3 36 ...
Page 244: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet ...
Page 249: ...5 2 Ping Test 5 2 2 Procedure 5 6 ...
Page 353: ...7 8 Other CompoNet Functions 7 8 2 Installing Expansion Modules 7 32 ...
Page 404: ...Appendices ...
Page 407: ...A 1 CPS File Management A 1 1 Description of CPS Files A 4 ...
Page 413: ......
Page 414: ......
Page 415: ......