Commissioning
PR 5500 Instrument Manual
EN-268 Sartorius
5.19.6.3 DeviceNet Settings for Rockwell Workstation
Requirements
-
The PR 1721/64 DeviceNet fieldbus card is installed; see Chapter 4.4.9.
-
The parameters have been selected and saved according to the weighing points (1x WP = 8 byte I/O);
see Chapter 5.19.6.1.
Procedure
t
t
Establish communication with the workstation in the ‚RSLinx‘ program (initial ser.DF1, recommended ETH-
LAN).
t
t
Register the file ‚sag_5500_DVN.EDS‘ in the ‚RSNetWorx for DeviceNet‘ program.
t
t
Add a database entry in the hardware window under
[Vendor] - [Sartorius Mechatronics T&H GmbH] -
[Communications Adapter]:
-
Drag ‚Scanner 1769 SDN‘ to ‚Graph‘ and enter slot number (e.g., 3).
-
Drag ‚MAXXIS Device‘ to ‚Graph‘ and apply the MAC ID specified on the instrument.
t
t
Start the ‚RSLogix5000‘ program.
t
t
Create a new project (‚New‘) with a hardware structure according to the hardware components and enter
Slot1…n.
t
t
In
[Backplane] -
[CompactBus Local] -
[1769-SDN/B], select [Properties Slot(n)].
t
y
The ‚Module Properties Report‘ window appears.
t
t
Enter values for input size [2/4/6/8] and output size [2/4/6/8] (32-bit) according to the active weighing
points (1x WP = 2 x 32-bit = 8 byte I/O).
t
t
Upload from the workstation to the project newly created with the <RSLogix5000> program.
t
t
In the <RSLogix5000> program, set the access to ‚Online‘ in
[Controller Tags] as [DINT per WP 2 lines
with 4 bytes each].
t
t
Additional settings are defined in the application in question, such as phase (see corresponding manual).
Card Test
The fieldbus card has 2 LEDs (MS, NS). Communication is functioning correctly when the LEDs are green
(see Chapter 4.4.9).
All inputs and outputs are displayed under [System maintenance] - [Test hardware] - [I/O card test] -
[Option-FB PR 1721/64].
Note
Further details can be found in the supplementary application manual ‚How to...‘ (available
upon request from [email protected]).
‚RSLinx‘, ‚RSNetWorx‘, and ‚RSLogix5000‘ are products of Rockwell Automation®.