Transmitter status reported by status LED
(continued)
Table 10-1:
LED state
Description
Recommendation
Red
One or more high-severity alerts are active.
A high-severity alert condition affects meas-
urement accuracy and output behavior. Re-
solve the alert condition before continuing.
Related information
View and acknowledge status alerts
10.6
Status alerts, causes, and recommendations
Alert num-
ber
Alert title
Possible cause
Recommended actions
A001
EEPROM Error
The transmitter has detected a
problem communicating with the
sensor.
•
Cycle power to the meter.
•
Contact Micro Motion.
A002
RAM Error
The transmitter has detected a
problem communicating with the
sensor.
•
Cycle power to the meter.
•
Contact Micro Motion.
A003
No Sensor Response The transmitter is not receiving one
or more basic electrical signals from
the sensor.
•
Check the drive gain and the pickoff
voltage. See
and
•
Check the integrity of the sensor tubes.
A004
Temperature Over-
range
The RTD resistance is out of range
for the sensor.
•
Check your process conditions against
the values reported by the device.
•
Verify temperature characterization or
calibration parameters.
•
Contact Micro Motion.
A005
Velocity Overrange
The measured velocity is greater
than the maximum velocity limit of
the sensor (
Δ
T greater than 200 µs).
•
If other alerts are present, resolve those
alert conditions first. If the current alert
persists, continue with the recommen-
ded actions.
•
Check your process conditions against
the values reported by the device.
•
Check for two-phase flow. See
A006
Characterization Re-
quired
Calibration factors have not been
entered, or the sensor type is incor-
rect, or the calibration factors are
incorrect for the sensor type.
•
Verify all of the characterization or cali-
bration parameters. See the sensor tag
or the calibration sheet for your meter.
•
Contact Micro Motion.
Troubleshooting
Configuration and Use Manual
143
Summary of Contents for CDM100M
Page 8: ...Getting Started 2 Micro Motion Compact Density Meters CDM ...
Page 12: ...Before you begin 6 Micro Motion Compact Density Meters CDM ...
Page 20: ...Configuration and commissioning 14 Micro Motion Compact Density Meters CDM ...
Page 26: ...Introduction to configuration and commissioning 20 Micro Motion Compact Density Meters CDM ...
Page 110: ...Integrate the meter with the control system 104 Micro Motion Compact Density Meters CDM ...
Page 116: ...Operations maintenance and troubleshooting 110 Micro Motion Compact Density Meters CDM ...
Page 124: ...Transmitter operation 118 Micro Motion Compact Density Meters CDM ...
Page 194: ...Using the transmitter display 188 Micro Motion Compact Density Meters CDM ...
Page 208: ...Using ProLink III with the transmitter 202 Micro Motion Compact Density Meters CDM ...