Configure HART burst messages
Display
Not available
ProLink III
Device Tools
>
Configuration
>
Communications
>
Communications (HART)
Field Communicator
Configure
>
Manual Setup
>
HART
>
Burst Mode
Overview
Burst messages contain information on process variables or transmitter status. You can
configure up to three burst messages. Each message can contain different information.
Burst messages also provide the mechanism for trigger mode and event notification.
Procedure
1.
Navigate to the burst message you want to configure.
2.
Enable the burst message.
3.
Set
Burst Option
to the desired content.
Options for burst message contents
Table 6-9:
HART
command
Label
Description
ProLink III
Field Communicator
1
Source (Primary Variable)
Primary Variable
The transmitter sends the primary variable (PV) in
the configured measurement units in each burst
message (e.g., 14.0 g/sec, 13.5 g/sec, 12.0 g/sec).
2
Primary Variable (Percent
Range/Current)
Pct Range/Current
The transmitter sends the PV’s actual mA level and
the PV’s percent of range in each burst message
(e.g., 11.0 mA 25%).
3
Process Variables/Current
Process Vars/Current
The transmitter sends the PV’s actual milliamp read-
ing and the PV, SV, TV, and QV values in measure-
ment units in each burst message (e.g., 11.8 mA,
50 g/sec, 23 °C, 50 g/sec, 0.0023 g/cm3).
9
Read Device Variables with
Status
Device Variables with Status
The transmitter sends up to eight user-specified
process variables in each burst message.
33
Transmitter Variables
Field Device Vars
The transmitter sends four user-specified process
variables in each burst message.
48
Read Additional Transmitter
Status
Read Additional Device Sta-
tus
The transmitter sends expanded device status infor-
mation in each burst message.
4.
Depending on your choice, select the four or eight user-specified variables for the
burst message, or set the HART variables as desired.
Integrate the meter with the control system
98
Micro Motion
®
Compact Density Meters (CDM)
Summary of Contents for CDM100M
Page 8: ...Getting Started 2 Micro Motion Compact Density Meters CDM ...
Page 12: ...Before you begin 6 Micro Motion Compact Density Meters CDM ...
Page 20: ...Configuration and commissioning 14 Micro Motion Compact Density Meters CDM ...
Page 26: ...Introduction to configuration and commissioning 20 Micro Motion Compact Density Meters CDM ...
Page 110: ...Integrate the meter with the control system 104 Micro Motion Compact Density Meters CDM ...
Page 116: ...Operations maintenance and troubleshooting 110 Micro Motion Compact Density Meters CDM ...
Page 124: ...Transmitter operation 118 Micro Motion Compact Density Meters CDM ...
Page 194: ...Using the transmitter display 188 Micro Motion Compact Density Meters CDM ...
Page 208: ...Using ProLink III with the transmitter 202 Micro Motion Compact Density Meters CDM ...