Modbus ASCII support
Available Modbus addresses
Disabled
1–127, excluding 111 (111 is reserved to the service port)
Enabled
1–15, 32–47, 64–79, and 96–110
2.
Set
Modbus Address
to a unique value on the network.
3.
Set
Floating-Point Byte Order
to match the byte order used by your Modbus host.
Code
Byte order
0
1–2 3–4
1
3–4 1–2
2
2–1 4–3
3
4–3 2–1
See the following table for the bit structure of bytes 1, 2, 3, and 4.
Bit structure of floating-point bytes
Table 6-10:
Byte
Bits
Definition
1
SEEEEEEE
S=Sign
E=Exponent
2
EMMMMMMM
E=Exponent
M=Mantissa
3
MMMMMMMM
M=Mantissa
4
MMMMMMMM
M=Mantissa
4.
(Optional) Set
Additional Communications Response Delay
in
delay units
.
A delay unit is 2/3 of the time required to transmit one character, as calculated for
the port currently in use and the character transmission parameters.
Additional Communications Response Delay
is used to synchronize Modbus
communications with hosts that operate at a slower speed than the device. The
value specified here will be added to each response the device sends to the host. The
default value is 0. Valid values range from 1 to 255.
Tip
Do not set
Additional Communications Response Delay
unless required by your Modbus host.
Integrate the meter with the control system
102
Micro Motion
®
Compact Density Meters (CDM)
Summary of Contents for CDM100M
Page 8: ...Getting Started 2 Micro Motion Compact Density Meters CDM ...
Page 12: ...Before you begin 6 Micro Motion Compact Density Meters CDM ...
Page 20: ...Configuration and commissioning 14 Micro Motion Compact Density Meters CDM ...
Page 26: ...Introduction to configuration and commissioning 20 Micro Motion Compact Density Meters CDM ...
Page 110: ...Integrate the meter with the control system 104 Micro Motion Compact Density Meters CDM ...
Page 116: ...Operations maintenance and troubleshooting 110 Micro Motion Compact Density Meters CDM ...
Page 124: ...Transmitter operation 118 Micro Motion Compact Density Meters CDM ...
Page 194: ...Using the transmitter display 188 Micro Motion Compact Density Meters CDM ...
Page 208: ...Using ProLink III with the transmitter 202 Micro Motion Compact Density Meters CDM ...