Field Communicator connection to multidrop network
Figure D-3:
A
C
D
B
E
A. Field Communicator
B. Devices on the network
C. External power supply (may be provided by the PLC)
D.
250–600
Ω
resistance (may be provided by the PLC)
E. Master device
4.
Turn on the Field Communicator and wait until the main menu is displayed.
5.
If you are connecting across a multidrop network:
•
Set the Field Communicator to poll. The device returns all valid addresses.
•
Enter the HART address of the transmitter. The default HART address is 0.
However, in a multidrop network, the HART address has probably been set to a
different, unique value.
Postrequisites
To navigate to the Online menu, choose
HART Application
>
Online
. Most configuration,
maintenance, and troubleshooting tasks are performed from the Online menu.
Tip
You may see messages related to the DD or active alerts. Press the appropriate buttons to ignore the
message and continue.
Using the Field Communicator with the transmitter
206
Micro Motion
®
Compact Density Meters (CDM)
Summary of Contents for CDM100M
Page 8: ...Getting Started 2 Micro Motion Compact Density Meters CDM ...
Page 12: ...Before you begin 6 Micro Motion Compact Density Meters CDM ...
Page 20: ...Configuration and commissioning 14 Micro Motion Compact Density Meters CDM ...
Page 26: ...Introduction to configuration and commissioning 20 Micro Motion Compact Density Meters CDM ...
Page 110: ...Integrate the meter with the control system 104 Micro Motion Compact Density Meters CDM ...
Page 116: ...Operations maintenance and troubleshooting 110 Micro Motion Compact Density Meters CDM ...
Page 124: ...Transmitter operation 118 Micro Motion Compact Density Meters CDM ...
Page 194: ...Using the transmitter display 188 Micro Motion Compact Density Meters CDM ...
Page 208: ...Using ProLink III with the transmitter 202 Micro Motion Compact Density Meters CDM ...