7
Completing the configuration
Topics covered in this chapter:
•
Test or tune the system using sensor simulation
•
Back up transmitter configuration
•
7.1
Test or tune the system using sensor
simulation
Display
Not available
ProLink III
Device Tools
>
Diagnostics
>
Testing
>
Sensor Simulation
Field Communicator
Service Tools
>
Simulate
>
Simulate Sensor
Overview
Use sensor simulation to test the system's response to a variety of process conditions,
including boundary conditions, problem conditions, or alert conditions, or to tune the
loop.
Procedure
1.
Enable sensor simulation.
2.
Set the process variables to the desired test values.
3.
Observe the system response to the simulated values and make any appropriate
changes to the transmitter configuration or to the system.
4.
Modify the simulated values and repeat.
5.
When you have finished testing or tuning, disable sensor simulation.
7.2
Back up transmitter configuration
ProLink II and ProLink III provide a configuration upload/download function which allows
you to save configuration sets to your PC. This allows you to back up and restore your
transmitter configuration. It is also a convenient way to replicate a configuration across
multiple devices.
Restriction
This function is not available with any other communications tools.
Completing the configuration
Configuration and Use Manual
105
Summary of Contents for CDM100M
Page 8: ...Getting Started 2 Micro Motion Compact Density Meters CDM ...
Page 12: ...Before you begin 6 Micro Motion Compact Density Meters CDM ...
Page 20: ...Configuration and commissioning 14 Micro Motion Compact Density Meters CDM ...
Page 26: ...Introduction to configuration and commissioning 20 Micro Motion Compact Density Meters CDM ...
Page 110: ...Integrate the meter with the control system 104 Micro Motion Compact Density Meters CDM ...
Page 116: ...Operations maintenance and troubleshooting 110 Micro Motion Compact Density Meters CDM ...
Page 124: ...Transmitter operation 118 Micro Motion Compact Density Meters CDM ...
Page 194: ...Using the transmitter display 188 Micro Motion Compact Density Meters CDM ...
Page 208: ...Using ProLink III with the transmitter 202 Micro Motion Compact Density Meters CDM ...