No.
Name
Outer Diameter
and Thickness
(mm)
Technical Requirements
5
Inverted trap of
liquid pipes
19.0x1.0
Inner diameters at the two
expanded ends of the copper pipe:
19.0 mm
6
Inverted trap of
liquid pipes
15.9x1.0
Inner diameters at the two
expanded ends of the copper pipe:
16.3 mm
Note: The surface of molded parts must be even.
4.2.2.4 Humidifier Water Inlet Pipe
Figure 4-23 Connecting a water inlet pipe
(1) Connector with outer screw
threads: G 3/4 inch
(2) Adapter with inner screw
threads: G 3/4 inch. Plastic
materials such as PA66 and
metal materials are
recommended.
(3) Matched with the adapter,
the pressure resistance should
be at least 0.7 MPa
NO TE
The object shown in the dotted line box is the water inlet pipe connector with outer screw
threads delivered with smart cooling products. Other parts are not provided and need to be
purchased.
4.2.2.5 Drainpipe
The drainpipe can be connected using a hose or a rigid pipe.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
4 System Installation
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
70