Ambient
Temperature
Proper
Discharge
Pressure Range
Proper Suction
Pressure Range
Proper
Overheating
Degree
> 45°C
3.1–4.15 MPa
NO TE
If the suction pressure, discharge pressure, and suction overheating degree is without
normal ranges, check and make sure that:
1. Charge refrigerant in an amount exactly as standard charge required. (Refrigerant
charging too much would result in high discharge pressure. Refrigerant charging too
little would result in low suction pressure, low discharge pressure, and high suction
overheating degree.)
2. The air inlet and outlet of outdoor unit are without block. (The air inlet and outlet
blockage would result in high discharge pressure.)
Step 5 After charging refrigerant, close all valves, restore the thermal insulation foam on
the needle valves.
Step 6 Tap
to exit the diagnostic mode.
Step 7 Tap Shutdown on the home screen and confirm it.
----End
6.8 Wizard Startup
Prerequisites
Check that refrigerant is fully charged before performing the wizard startup.
Context
Wizard startup allows for commissioning of components such as the indoor fan,
electric heater, humidifier, and cooling system. It also supports component
automatic operation and automatic device checking, and can output a
commissioning report.
After you power on the smart cooling product for the first time, the screen
displays the Wizard Startup screen. If the smart cooling product is not started for
the first time, choose Maint > Wizard Startup to enter the Wizard Startup
screen.
NO TICE
Tapping No or Exit, submission timeout, and system exception all result in
commissioning failures. Choose Maint > Wizard Startup to enter the Wizard
Startup screen for new commissioning.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
6 Power-On Commissioning
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
200