Parameter
Description
SSH (LAN)
● Enable: Access to the unit through the intranet using
SSH (default port number: 22) is allowed.
● Disable: Access to the unit through the intranet
using SSH is not allowed.
● If this parameter is set to Disable, the function will
be enabled within 30 minutes after power-on by
default.
● If this parameter is set to Enable, the function will
be automatically disabled after 24 hours of running.
----End
6.5.4.2 Setting Communications Parameters (Modbus-RTU Protocol)
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > Modbus Settings.
Figure 6-23 Modbus Settings
Step 2 Set the baud rate, communication address, and RS485 monitoring group.
Parameter
Description
Baud rate
Set this parameter based on the baud rate of the
connected device. The baud rate must be the
same as that on the NMS. The value can be 9600
or 19200.
Communication address
Enter the communications address of the smart
cooling product as planned. The NMS
communicates with the smart cooling product
using this address, and the communications
addresses of two smart cooling products
connected to the same NMS must be different.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
6 Power-On Commissioning
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
189