Figure 4-11 Top view of vertical installation space for the NetCol500-A080 with an
air baffle (unit: mm)
Figure 4-12 Horizontal installation space for an outdoor unit with a low
temperature component (for NetCol500-A060) (unit: mm)
NO TE
1. The distance from the low temperature component to the outdoor unit cannot exceed 2
m.
2. When installing an outdoor unit vertically, do not place a low temperature component
at the air exhaust vent. Keep the low temperature component 600–2000 mm away from
the outdoor unit.
3. When the outdoor unit is installed horizontally, the outdoor unit and the low-
temperature component must be placed at the same height of base or concrete
platform. When an outdoor unit is installed vertically, the outdoor unit must not be
lower than the low-temperature component, and the height difference cannot exceed
1.5 m.
Compact installation scenario
NO TE
If the space does not meet the requirements of the recommended layout, you can use any
of the following layouts (applicable only to NetCol500-A060, NetCol500-A110 and
NetCol500-A120). However, the cooling capacity of indoor units will be reduced. Exercise
caution when deciding to select the non-recommended layouts.