Symptom
Possible Cause
Solution
An indoor
fan fails to
start.
The switch of the indoor fan is
not turned on.
Check the switch of the indoor
fan.
An indoor fan is damaged.
Replace the indoor fan.
The interconnection terminals
for the fans are not securely
connected.
Secure the interconnection
terminals again.
The
heating
function is
unavailable
.
The electric heater
temperature switch is being
protected.
Check the temperature switch
and replace it if it is faulty.
The electric heater is not
switched on.
Check the electric heater switch.
An electric heater is burnt out. Disconnect the power supply and
check whether the electric heater
is damaged by checking the
electric heater resistance
properties with an ohmmeter.
No water is
supplied to
the water
inlet
solenoid
valve of
the
humidifier.
The upstream water supply is
faulty or the water pressure is
below the lower threshold.
Restore the water supply.
The water inlet solenoid valve
is blocked or faulty.
Replace the water inlet solenoid
valve.
The cable to the water inlet
solenoid valve is incorrectly
connected.
Reconnect the cable.
The water
overflows
the
NetCol800
0-A.
The liquid level detector is
faulty.
Check the alarm. Check cable
connections for high and low
liquid level detectors. Check
whether the liquid level detectors
are damaged. If necessary,
replace the liquid level detectors.
The inlet pipe and drainpipe
leak.
Check the inlet pipe and
drainpipe and the connectors.
Rectify any leakage and fasten
the connectors.
The self-drainpipe is blocked.
Check that no blocks and frost in
the self-drainpipe.