Tab
Parameter
Description
Comm
Settings
Modbus Comm
address
Enter the communication address
planned for the smart cooling product.
The management system
communicates with the smart cooling
product through this address. The
communication addresses of the two
smart cooling products connected to
the same management system must
be different.
Step 5 After power-on, the compressor starts preheating, and the system generates an
alarm indicating that the compressor is preheating. Do not start the smart cooling
product before the preheating is complete. Choose Running > Device Details >
Compressor to view the remaining preheating time of the compressor.
●
If the return air temperature is greater than 10°C upon power-on, the
preheating time is 6 hours.
●
If the return air temperature is less than or equal to 10°C or invalid upon
power-on, the preheating time is 12 hours.
----End
6.4 Home Screen
You can tap the menu items, buttons, or icons on the screen to enter related
screens or perform operations, such as Running, Alarms and Settings. The home
screen is shown in
NO TICE
The information in the screenshots is for reference only. The actual parameters
may vary.
Figure 6-18 Home screen
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
6 Power-On Commissioning
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
177