solution from corroding pipes, corrosion inhibitor should be mixed into the
glycol solution. For details about the mixing scheme, consult glycol experts.
●
Wrap thermal insulation layers for pipes connecting the water-cooled module.
●
A maximum of four water-cooled modules can be stacked, as shown in the
following figure.
Figure 4-18 Stacking scenario
(1) Water strainer
●
The water-cooled module should be installed on a concrete base. The base
requirements are as follows.
Figure 4-19 Concrete base dimensions (unit: mm)
(1) Mounting hole: 4 x M12
●
The following figure shows the operation area requirements for water-cooled
modules.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
4 System Installation
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
62