Figure 4-97 Connecting the signal cable to the water-cooled module
(A) Core wire
(B) Insulation layer
(C) Shield layer
(D) Jacket
NO TE
● If the indoor unit is NetCol8000-A090 or NetCol8000-A120, connect the outdoor unit
signal cable to x503 terminals 1, 2, and 3, or 5, 6, and 7 of the indoor unit.
● The RS485 signal cable from the indoor unit to the outdoor unit must be routed away
from the power cable. The distance between the signal cable and the power cable must
be at least 30 mm.
● It is recommended that a shielded twisted pair be used as the RS485 signal cable from
the indoor unit to the outdoor unit.
● The shield layer of the signal cable must be grounded.
4.11.3.2 Connecting Water Sensor Cables
Context
A water sensor monitors resistance changes at terminals to determine whether
the floor is watery. When the terminals of a water sensor detect water or other
conductive liquid, resistance between the two terminals decreases. Keep water
sensors far away from water traps or floor drains.
Procedure
Step 1 Connect one end of the water sensor cable to the water sensor.
Step 2 Connect the other end of the water sensor cable to 1 and 2 on signal terminal
x502 through the signal cable hole at the bottom of the cabinet.