Category
Tool
Nitrogen
f
Antifreeze gloves
Electronic
balance
(measurement
range: ≥ 20 kg)
Multimeter
Clamp meter
Thermocouple
temperature
sensor
-
-
c: The flow rate of the vacuum pump should range from 2 L/s to 4 L/s. The
absolute vacuum degree should be 60 Pa at most.
d: The pressure gauges and rubber hoses must be dedicated for R410A. The
measuring range of the pressure gauges must be at least 4.0 MPa, and the
rubber hoses must withstand a pressure of at least 4.5 MPa. Ensure that the
rubber hoses match the 1/4 inch needle valves inside the unit. If necessary,
prepare needle valve adapters. When charging refrigerant, you are advised to
use a safety valve to prevent refrigerant leakage during the removal of a
rubber hose, which may cause frostbite.
e: The nitrogen cylinder port should have a reducing valve, and the measuring
range should be at least 4.0 MPa.
f: Dry nitrogen.
4.2.2 Materials
Item
Description
Type
Standard
material
This type of materials is
provided by Huawei, and you
can find them in the fittings
delivered with the equipment.
Materials in the packing list
Auxiliary
material
Customers can purchase this
type of materials from Huawei
or other vendors.
Refrigerant, refrigerant oil,
refrigerant pipe component,
and cable
Optional
material
Purchased from Huawei based
on application scenarios.
Low temperature component,
T/H sensor, water sensor, and
smoke sensor
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
4 System Installation
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
66