Require password to
start or shut down
onsite
● No: No password is required for
startup or shutdown.
● Yes: A password is required for
startup and shutdown.
Heating function
● Enable: The device starts
humidifying when the ambient
temperature is lower than the
temperature setpoint by a certain
range.
● Enabled when active power supply
is working: The device starts
heating only when the active power
supply is used and the ambient
temperature is lower than the
temperature setpoint by a certain
range. (The electric heater is an
auxiliary function. By default, it is
enabled when the active power
supply is used and is disabled when
the standby power supply is used.)
● Disable: The heating function is
disabled.
Heating mode
This parameter can be set to
Dehumidifying heating, Low-
temperature heating, or
Dehumidification & Low
temperature heating.
● Dehumidifying heating: When the
dehumidifying function is enabled,
the electric heater is started to
supplement the cooling capacity to
achieve dehumidification at
constant temperature.
● Low-temperature heating: The
heating function is enabled when
the current temperature is lower
than the temperature setpoint by a
certain value.
● Dehumidification & Low
temperature heating: Both
functions are available.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual