4.9 Leakage Test with Nitrogen
Prerequisites
NO TICE
● Pipes from indoor unit and outdoor unit have been welded properly.
● The needle valve plugs are tightened.
● The measuring range of the pressure gauge must be greater than or equal to
4.0 MPa, and the tolerance range of the leather hose must be greater than or
equal to 4.5 MPa.
● Only nitrogen is allowed when leak checking.
● Do not remove the pressure gauge and the leather hose when charging
nitrogen to retain the pressure to prevent the nitrogen from leaking.
Procedure
Step 1 Connect a leather hose, pressure gauge, reducing valve, and nitrogen cylinder to
the equipment. Ensure that the pressure gauge and reducing valve are closed.
●
If no low-temperature component is installed on the outdoor side, connect
pipes as shown in
, and charge nitrogen into the system from the
low-pressure and exhaust pipe needle valves simultaneously.